(a) The tolerances prescribed in this chapter for electric meters and the meter's accessories apply equally to errors of under-registration and to errors of over-registration. (b) The acceptance and maintenance tolerance for demand meters, meter accessories, instrument transformers, and all other devices used to measure electrical energy sold to consumers is plus or minus two percent. When devices are used in combination, the total combined error may not exceed plus or minus two percent.
Authorities
45.75.040;45.75.050;45.75.070;45.75.080