Section 18.78.010. Minimum requirements.  


Latest version.
  • 	(a)  A person who owns or operates a UST, or who intends to install, have installed, return to operation, or acquire ownership of a UST shall meet the requirements of 18 AAC 78.015. If the UST is closed, the owner or operator shall notify the department as required by 18 AAC 78.085(a).  
    	(b)  A person may not install a UST, including a UST described at 18 AAC 78.005(f), to store petroleum unless the UST, whether of single-wall or double-wall construction,  
    		(1) will prevent a release caused by corrosion or structural failure for the operational life of the system;  
    		(2) is cathodically protected against corrosion, constructed of noncorrodible material, steel clad with a noncorrodible material, or designed to prevent the release or threatened release of a stored petroleum; and  
    		(3) is constructed or lined with a material that is compatible with the stored petroleum, as provided at 18 AAC 78.050.  
    