Section 8.80.070. Low-water fuel cutoff.  


Latest version.
  • 	(a)  An automatically fired steam boiler must be equipped with an automatic low-water fuel cutoff.  
    	(b)  An automatically fired hot water heating or hot water supply boiler that exceeds an input of 400,000 Btu per hour must be equipped with an automatic low-water fuel cutoff or a loss of flow switch, as appropriate for the heater or boiler.  
    

Authorities

18.60.180

Notes


Authority
AS 18.60.180
History
Eff. 6/21/84, Register 90; am 12/17/99, Register 152